Chiller Condenser Evaporator Heat Exchanger Oil Cooler Spray Evaporator Falling Film Spray Cooler Falling Film Spray Chiller Thermosyphon Shell Tube Plate and Frame Shell and Plate Brazed Plate Compact Brazed Refrigeration System Refrigerant Air Conditioning Cooling Heating Heat Recovery Freezing Boiling Beverage Industry Soft Drink Industry Poultry R-22 Ammonia R-134a CFC HCFC Marine Application RSW Refrigerated Sea Water Titanium Laser Welded ASME Compressor Packaged Chiller Industrial Refrigeration Engineered Systems Air Conditioning Cooling Heating Heat Recovery Freezing Boiling Beverage Industry Soft Drink Industry Poultry
Home
Contact us
E-mail
Home Contact Us Send us E-mail
  Home > Tech. Corner > case studies > Ammonia Flooded Evaporator
 

case studies

Selecting appropriate enhancement is a key to an optimized heat exchanger. The final goal must be to achieve the ratio of outside heat transfer coefficient to inside heat transfer coefficient as one (ho/hi = 1). Table 1 shows the design parameters and output data. The final selection for this application was based on the basis of ho/hi close to one. Therefore, case C, with inside enhancement was selected as an optimized design. Enhancement was achieved via twisted tape turbulators with H/D = 4.1, tape width 0.5” (12.7 mm), and thickness 0.025” (0.635 mm). Selection D would had been satisfactory too but it would have resulted in 20% extra cost and 50% extra pump power requirement. The unit was installed and has been operational for several years with no thermal or mechanical problems.

Table 1 Comparative case study of ammonia flooded evaporator
Parameter
A
B
C
D
Shell OD, in (mm)
16 (406.4)
16 (406.4)
16 (406.4)
16 (406.4)
Tube OD, in (mm)
0.75 (19)
0.75 (19)
0.75 (19)
0.75 (19)
Tube wall, in (mm)
0.065 (1.65)
0.049 (1.245)
0.065 (1.65)
0.049 (1.245)
Passes
2
2
2
2
Under/over capacity
-78%
-75%
0%
+6%
Pressure drop, psi (bar)
20.0 (1.38)
35.0 (2.41)
6.8 (0.47)
10.8 (0.74)
ho/hi
2.90
4.10
1.20
1.87
Design capacity: 487,200 Btu/hr (143 kW)
Refrigerant:       Ammonia @ -40°F (-40°C) saturated temperature
Process fluid:     29% wt/wt CaCl2 brine
Process flow:      450 gpm (28.4 l/s)
Process inlet:    -29.4°F (-34.1°C)
Process outlet:  -32°F (-35.6°C)
A:     No enhancement
B:     Outside enhancement only
C:     Inside enhancement only
D:     Both sides enhanced

 
 
©Copyright 2006 Isotherm Australia Reserved.
Australian Contact:
8/47-51 Boundary Street, Parramatta
Parramatta, New South Wales (NSW) Australia.
Voice: + 61 410 622 946 Fax: +61 2 8212 5994
e-mail: info@isotherm.com.au

Headquarters:
7401 Commercial Blvd.East
Arlington, Texas 76001
Voice: 817-472-9922 Fax: 817-472-5878
e-mail: info@iso-therm.com
Developed By:
Naxtor Technologies